Place of Origin: | UK |
Brand Name: | MTL |
Certification: | ccs2 |
Model Number: | MTL5575 (THC or RTD input + Alarm) |
Minimum Order Quantity: | 1 |
---|---|
Price: | 50USD per piece |
Packaging Details: | Carton |
Delivery Time: | one week |
Payment Terms: | T/T |
MTL5575 (THC or RTD input + Alarm)
Why do you choose us?
1. 100% original package product, 100% quality assurance.
If you find a fake product. Please contact us without hesitation! We afford the shipment cost! We send you a new product asking zero cent!
2. Varied payment methods.
We adopt Paypal, T/T, Alibaba Trade Assurance order, and other methods. If you can not trust us , you can choose to pay it via Ali-express! 100% make your money safe!
We mainly supply Yokogawa pressure transmitter, Emerson 475 field communicator, Emerson AMS Trex Device communicator, Siemens pressure transmitter, Honeywell transmitter, and the Honeywell BW gas analytics.
Wuhan Xieyuan Automation Equipment Co., Ltd
Telephone:86-027-85583233
Mobile Phone:86-18671080257
Fax:86-027-85309780
Contact : victor@whxyauto.com
Skype:victordu963@gmail.com
Whatsapp & Viber are available
Address:6-C9,Caishen Commercial Plaza,Hankou Railway Station
MTL5575 (THC or RTD input + Alarm)
MTL5575 (THC or RTD input + Alarm)
MTL5575 converts a low-level dc signal from a temperature sensor mounted in a hazardous area into a 4/20mA current for driving a safe-area load. Software selectable features include linearisation, ranging, monitoring, testing and tagging for all thermocouple types and 2-, 3- or 4-wire RTDs. (For thermocouple applications the HAZ-CJC plug on terminals 1–3 includes an integral CJC sensor). Configuration is carried out using a personal computer. A single alarm output is provided and may be configured for process alarm or to provide notice of early thermocouple failure.
MTL5575 SPECIFICATION
See also common specification
Number of channels
One
Signal source
THC types J, K, T, E, R, S, B or N to BS 60584 and XK
MV input
RTDs 2/3/4-wire platinum to BS 60751
Pt 100, Pt 500, Pt 1000
Cu-50 & Cu-53
Ni 100/500/1000 DIN 43760
Location of signal source
Zone 0, IIC, T4-6 hazardous area
Division 1, Group A, hazardous location
Input signal range
–75 to +75mV, or 0 to 400Ω (0 to 1000Ω Pt & Ni sensors)
Input signal span
3 to 150mV, or 10 to 400Ω (10 to 1000Ω Pt & Ni sensors)
RTD excitation current
200µA nominal
Cold junction compensation
Automatic or selectable
cold junction compensation error
≤ 1.0°C
Common mode rejection
120dB for 240V at 50Hz or 60Hz (500ms response)
Series mode rejection
40dB for 50Hz or 60Hz
Calibration accuracy (at 20°c)
(includes hysteresis, non-linearity and repeatability)
Inputs: (500ms response)
MV/THC: ± 15µV or ± 0.05% of input value
(whichever is greater)
RTD: ± 80mΩ
Output: ± 11µA
Temperatures drift (typical)
Inputs:
mV/THC: ± 0.003% of input value/°C
RTD: ± 7mΩ/°C
output: ± 0.6µA/°C
example of calibration accuracy and temperature drift
(rTD input - 500ms response)
Span: 250Ω
Accuracy: ± (0.08/250 + 11/16000) x 100%
= 0.1% of span
Temperature drift: ± (0.007/250 x 16000 + 0.6) µA/°C
= ±1.0µA/°C