Place of Origin: | UK |
Brand Name: | MTL |
Certification: | ccs2 |
Model Number: | MTL5581 (Isolator for low-level signals) |
Minimum Order Quantity: | 1 |
---|---|
Price: | 50USD per piece |
Packaging Details: | Carton |
Delivery Time: | one week |
Payment Terms: | T/T |
MTL5581 (Isolator for low-level signals)
Why do you choose us?
1. 100% original package product, 100% quality assurance.
If you find a fake product. Please contact us without hesitation! We afford the shipment cost! We send you a new product asking zero cent!
2. Varied payment methods.
We adopt Paypal, T/T, Alibaba Trade Assurance order, and other methods. If you can not trust us , you can choose to pay it via Ali-express! 100% make your money safe!
We mainly supply Yokogawa pressure transmitter, Emerson 475 field communicator, Emerson AMS Trex Device communicator, Siemens pressure transmitter, Honeywell transmitter, and the Honeywell BW gas analytics.
Wuhan Xieyuan Automation Equipment Co., Ltd
Telephone:86-027-85583233
Mobile Phone:86-18671080257
Fax:86-027-85309780
Contact : victor@whxyauto.com
Skype:victordu963@gmail.com
Whatsapp & Viber are available
Address:6-C9,Caishen Commercial Plaza,Hankou Railway Station
MTL5581 (Isolator for low-level signals)
MTL5581 (Isolator for low-level signals)
MTL5581 takes a low-level dc signal from a voltage source in a hazardous area, isolates it, and passes it to a receiving instrument located in the safe area. The module is intended for use with thermocouples utilising external cold-junction compensation. A switch enables or disables the safety drive in the event of thermocouple burnout or cable breakage; a second switch permits the selection of upscale or downscale operation as appropriate.
MTL5581 SPECIFICATION
See also common specification
Number of channels
One
Signal source
Any dc millivolt source
Location of millivolt source
Zone 0, IIC, T4–T6 hazardous area if suitably certified
Div. 1, Group A, hazardous location
Input and output signal range
0 to ± 50mV, overrange to ± 55mV
Maximum lead resistance 600Ω
Output resistance
60Ω nominal
Transfer accuracy@20°c
Linearity and repeatability < 0.05% of reading or ± 5μV,
Whichever is the greater
Temperature drift
< 2μV/°C, maximum
Response time
Settles to within 10% of final value within 150μs
Frequency response
dc to 4kHz nominal
Safety drive on THc burnout
Two switches enable or disable the safety drive and select