Place of Origin: | UK |
Brand Name: | MTL |
Certification: | ccs2 |
Model Number: | MTL5511 (1-channel, with line fault detection) |
Minimum Order Quantity: | 1 |
---|---|
Price: | 50USD per piece |
Packaging Details: | Carton |
Delivery Time: | one week |
Payment Terms: | T/T |
MTL5511 (1-channel, with line fault detection)
Why do you choose us?
1. 100% original package product, 100% quality assurance.
If you find a fake product. Please contact us without hesitation! We afford the shipment cost! We send you a new product asking zero cent!
2. Varied payment methods.
We adopt Paypal, T/T, Alibaba Trade Assurance order, and other methods. If you can not trust us , you can choose to pay it via Ali-express! 100% make your money safe!
We mainly supply Yokogawa pressure transmitter, Emerson 475 field communicator, Emerson AMS Trex Device communicator, Siemens pressure transmitter, Honeywell transmitter, and the Honeywell BW gas analytics.
Wuhan Xieyuan Automation Equipment Co., Ltd
Telephone:86-027-85583233
Mobile Phone:86-18671080257
Fax:86-027-85309780
Contact : victor@whxyauto.com
Skype:victordu963@gmail.com
Whatsapp & Viber are available
Address:6-C9,Caishen Commercial Plaza,Hankou Railway Station
MTL5511 (1-channel, with line fault detection)
MTL5511 (1-channel, with line fault detection)
Enables a safe area load to be controlled by a switch or proximity detector located in a hazardous area. When selected, open or short circuit conditions in the field wiring are detected by the line fault detect (LFD) facility and also indicated on the top of the module. Phase reversal for the channel is selected by a switch on the side of the module and output is provided by changeover relay contacts.
SPECIFICATION
See also common specification
Number of channels
One
Location of switches
Zone 0, IIC, T6 hazardous area
Div. 1, Group A hazardous location
Location of proximity detector
Zone 0, IIC, T4–6 hazardous area if suitably certified
Div. 1, Group A hazardous location
Hazardous-area inputs
Inputs conforming to BS EN60947–5–6:2001 standards for
Proximity detectors (NAMUR)
Voltage applied to sensor
7 to 9V dc from 1kΩ ±10%
Input/output characteristics
Normal phase
Outputs closed if input > 2.1mA (< 2kΩ in input circuit)
Outputs open if input < 1.2mA (> 10kΩ in input circuit)
Hysteresis: 200μA (650Ω) nominal
Line fault detection (LFD) (when selected)
User-selectable via switches on the side of the unit.
A line fault is indicated by an LED.
The channel output relay is de-energised if an input line fault is detected.
Open-circuit alarm on if Iin < 50μA
Open-circuit alarm off if Iin > 250μA
Short-circuit alarm on if Rin < 100Ω
Short-circuit alarm off if Rin > 360Ω
Note: Resistors must be fitted when using the LFD facility with a contact input
500Ω to 1kΩ in series with switch
20kΩ to 25kΩ in parallel with switch
Safe-area output
Single pole relay with changeover contacts
Note: reactive loads must be adequately suppressed